CABO PROFIBUS DP (6XV1830-0EH10 – 3079A)

Profibus SK Indoor + Outdoor have a special structure for processing with the Fast Connect Stripping Tool from Siemens. The indoor version is used for normal requirements in fixed installation applications in equipment; the Outdoor version is used in open-air applications, i.e. can withstand wind, weather and sun (not for burial directly in the ground).

Descrição

Type Cable structure Fixed installation, indoor 1x2x0.64 mm Fixed installation, outdoor 1x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 22/1)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: rd, gn rd, gn
Stranding element: Double core Double core
Separator: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: PVC PVC
Shielding 1: Al-Foil Al-Foil
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PE
Cable external diameter: app. 8,0 mm ± 0,4 mm app. 8,0 mm ± 0,4 mm
Outer sheath colour: Violet similar to RAL 4001 Black similar to RAL 9005
Electrical data Fixed installation, indoor 1x2x0.64 mm Fixed installation, outdoor 1x2x0.64 mm
Characteristic impedance: 150 Ohm ± 10 % 150 Ohm ± 10 %
Conductor resistance, max.: 55 Ohm/km 55 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 110 Ohm/km max. 110 Ohm/km max.
Mutual capacitance: 35 nF/km nom. 35 nF/km nom.
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 2,5 dB/km
38,4 kHz < 4,0 dB/km
4,0 MHz < 22,0 dB/km
16,0 MHz < 42,0 dB/km
9,6 kHz < 2,5 dB/km
38,4 kHz < 4,0 dB/km
4,0 MHz < 22,0 dB/km
16,0 MHz < 42,0 dB/km
Technical data Fixed installation, indoor 1x2x0.64 mm Fixed installation, outdoor 1x2x0.64 mm
Weight: app. 79 kg/km app. 65 kg/km
bending radius, repeated: 120 mm 120 mm
Operating temperature range min.: -40°C -20°C
Operating temperature range max.: +80°C +70°C
Caloric load, approx. value: 1,068 MJ/m 1,451 MJ/m
Copper weight: 24,00 kg/km 24,00 kg/km
Norms Fixed installation, indoor 1x2x0.64 mm Fixed installation, outdoor 1x2x0.64 mm
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170
Flame-retardant acc. to IEC 60332-3
Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CMG 75°C or CL3 or AWM 21694 600V
CSA standard: CSA FT 4