CABO DE REDE S/FTP CAT 6A

HELUKAT® 500IND was designed specially for extreme industrial applications for fixed installation. The copper data cable is especially well-suited for Category 6A10 Gigabit/500MHz (IEC 61156-5) Ethernet applications. It guarantees excellent transmission characteristics and may be used even under the harshest conditions.

Descrição

Type Cable structure Industrial Area S/FTP 4x2xAWG 22/1
Inner conductor diameter: Copper, bare (AWG 22/1)
Core insulation: Foam-skin-PE
Core colours: wh/bu, wh/og, wh/gn, wh/bn
Stranding element: Double core
Separator:
Inner sheath material: FRNC
Shielding 1: Al-Foil
Total shielding: AL-Foil + braid
Drain wire: yes
Outer sheath material: PVC
Cable external diameter: app. 9,6 mm ± 0,3 mm
Outer sheath colour: Green similar to RAL 6018
Electrical data Industrial Area S/FTP 4x2xAWG 22/1
Characteristic impedance: 100 Ohm ± 15 Ohm at 1 to 100 MHz
100 Ohm ± 20 Ohm at 101 to 500 MHz
Conductor resistance, max.: 59 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km
Loop resistance: 118 Ohm/km max.
Mutual capacitance: 72 nF/km nom.
Test voltage: 0,7 kV
Relative propagation velocity: 62%

Typical values

Frequency (MHz) 10 16 62,5 100 250 500
Attenuation (db/100m) 5,9 7,5 15,0 19,1 31,1 45,3
Next (dB) 60,3 57,2 48,4 45,3 39,3 34,8
PSNext (dB) 57,3 54,2 45,4 42,3 36,3 31,8
Technical data Industrial Area S/FTP 4x2xAWG 22/1
Weight: app. 115 kg/km
bending radius, repeated: 80 mm
Operating temperature range min.: -20°C
Operating temperature range max.: +60°C
Caloric load, approx. value: 1,63 MJ/m
Copper weight: 44,00 kg/km

Norms

Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 6A, Flame-retardant acc. to IEC 60332-3, CMG FT4

Part no. 803693, INDUSTRIAL ETHERNET KAT.6A 10GIG PVC